Achieving "Near Zero" Refrigerant Emissions in HVAC
Systems
Robert Johnson, Environmental Support Solutions
Introduction
The leak repair requirements, under Title VI Section 608
of the Clean Air Act Amendments of 1990, require that when
an owner or operator of an appliance that normally contains
a refrigerant charge of more than 50 pounds discovers that
refrigerant is leaking at a rate that would exceed the applicable
trigger rate during a 12-month period, the owner or operator
must take corrective action. The Clean Air Act also requires
that refrigerant vented into the atmosphere during installation,
service or retirement of equipment be minimized.
Trigger Rates
For all appliances that have a refrigerant charge of more
than 50 pounds, the following leak rates for a 12-month period
are applicable:
- commercial refrigeration 35%
- industrial process refrigeration 35%
- comfort cooling 15%
- all other appliances 15%
| Proposed Maximum
Permissable Leak Rates |
 |
Chiller Leak Prevention
Chillers and their refrigerants require ongoing preventative
maintenance. Preventing refrigerant from leaving, preventing
air from entering, and preserving refrigerant quality are all
a part of chiller maintenance. By maintaining your chillers
and by preventing chiller leaks you will also keep your operating
costs down.
Plant personnel should perform monitoring procedures daily
to minimize refrigerant discharge into the atmosphere. For
machines with refrigerants operating below atmospheric pressure,
technicians should check and log the purge system pump-out
rate. Other items to be logged daily include system supply
and return water temperatures, as well as refrigerant temperatures,
levels and pressures.
Look for "Evidence" and/or "Signs" of Leaks
Technicians should check the vane operator shaft, bearings
and joints, and drain the drip leg from the rupture disk discharge
line for oil seepage. Negative pressure machines such as those
using HCFC-123 should undergo maintenance, including compressor
valve plate replacement, and cleaning of the purge oil separator,
purge drum and purge condensing coil. This annual maintenance
also should include changing the purge oil and replacing the
purge valve seat as applicable.
Typically, chiller refrigerant oil was changed annually,
but the modern practice is to take a sample of the oil to a
laboratory to determine when the oil change is actually required.
The laboratory typically will check the oil for moisture, acid
and metals.
Minimizing oil changes is desirable, as refrigerant is dissolved
in the oil and could be released into the atmosphere when the
oil is discarded. Vacuum recovery units can reclaim refrigerants
that would have otherwise been lost in the oil change process.
Any technician performing an oil change must be certified
to work with refrigerants, and they must dispose of all waste
oil in compliance with applicable environmental regulations.
Technicians also should replace the oil filter along with the
oil, or more frequently if excessive differential pressure
readings across it dictate.
Tube check
Technicians also should check chiller condenser tubes annually
and evaporator tubes on closed systems should be checked every
three years. If tubes need cleaning and the interiors of the
tubes are smooth bore, technicians can remove the sludge with
bristle brushes attached to long metal rods. If the tubes contain
interior baffles, contact the chiller manufacturer’s representative
for information on how to clean their interiors.
After the brush cleaning, flush the tubes with clean water.
Scale deposits are cleaned chemically, typically by the water
treatment contractor. Proper water treatment including chemicals
and metering pumps in the condenser line minimizes the need
to clean fouled condenser water tubes. Cooling tower sumps
also must be kept treated and clean.
If proper chemical treatment of the condenser and cleaning
of the tubes has not been performed, then the tubes may be
pitted and need replacement.
Operations log
The importance of a log system cannot be over emphasized,
as it can provide early detection of deteriorating conditions,
inefficient operations, and refrigerant leaks.
Minimizing Leaks Requires Leak Management Plan
Restrictions on refrigerant releases and regulations on mandatory
leak repairs have made chiller leak management and refrigerant
conservation more important than ever. Maintenance engineers
must be properly trained, and must know what the specific regulations
and requirements are in order to effectively manage refrigerant
leaks and comply with EPA requirements.
While any maintenance engineer who services or oversees chillers
should be knowledgeable about traditional preventive maintenance
procedures for chillers, as well as steps to minimize refrigerant
discharge, some of the maintenance steps that involve refrigerant
handling and transfer must be performed by technicians who
are specially trained and EPA certified to do such work. Penalties
for letting uncertified personnel service refrigeration equipment
are substantial. Implementing a defined Leak Management Program
that incorporates regulatory requirements and good maintenance
practices is one of the key components of successful refrigerant
compliance management.
What Actions Should a Maintenance Professional Take?
Today, the new regulations, rising prices of refrigerants,
and reduction of energy efficiency of improperly charged refrigerant
chillers demand a more comprehensive and sophisticated approach
to refrigerant conservation and leak management. A Leak Management
Program should include the following:
- Conduct an Inventory of Equipment and Refrigerants
- Develop a Leak Management Plan
- Implement a Refrigerant Recordkeeping System
- Maintain Existing Equipment and Refrigerant Supplies
- Replace Old or Inefficient Equipment
Conduct an Inventory of Equipment and Refrigerants
Detailed records of equipment stocks and refrigerant are
essential for making informed decisions about refrigerant usage
and leak management. Priority should be given to equipment
with the largest charge. Inventory sheets should individually
list chillers and pieces of commercial refrigeration equipment.
Information is needed on the manufacturer, model, serial number,
year installed, capacity in tons, charge size, leak rates (based
on records of recharging or 'topping off'), refrigerant, and
location. Small appliances--such as household refrigerators
and window air conditioners, package units, vending machines,
water coolers, and ice machines should--also be inventoried
and can be recorded as groups.
The quantity of refrigerant purchased, consumed, disposed,
or reclaimed should be monitored and analyzed. Refrigerant
inventories should be kept by type and should include the volume
contained in each piece of existing equipment, as well as amounts
that are currently stored. These inventories should be updated
regularly. Local codes for storage limits should be consulted.
Develop a Leak Management Plan
A good plan is based on accurate equipment and refrigerant
inventories and usage. The plan should address compliance with
applicable laws and regulations, continued supplies and service,
reduced emissions, and recovery/ recycling. The plan should
emphasize responsible refrigerant handling practices.
Company’s polices and procedures regarding each of the following
issues should be included:
- Refrigerant purchase, sales and disposal
- Safe transport of refrigerants
- Refrigerant tracking and record keeping
- Contaminated refrigerant guidelines
- leak testing, leak prevention and leak repairs
- Equipment and refrigerant inventory
- Refrigerant storage
- Certification for technicians
- Penalties for noncompliance
- Compliance audits and surveys
- Refrigerant recovery, recycling, and reclaiming
- Servicing practices
- Refrigerant cylinder handling
- Venting and losses.
Reduce Operating Costs
Operational costs can rise without proper refrigerant management.
As refrigerant quality drops, the compressor must work harder,
drawing more power. The same applies to inadequate quantities
of refrigerant. Overcharged chillers face an even greater risk
of compressor damage than undercharged chillers.
With such a high value and impact on operations, it would
seem reasonable to expect that steps be taken to maintain refrigerant
quality and containment to avoid replacement.
Refrigerant management should include steps to ensure the
refrigerant’s quality and to keep the chiller as tight as possible.
Facilities must contain, convert or replace the CFCs in their
chillers. Facilities should not be reluctant to start the replacement
or retrofit of their chillers. With increased enforcement activity
by the EPA, non-compliance can result in fines and penalties
of up to $27,500 per day in civil penalties, up to 5 years
federal imprisonment for knowing or willful violations, and
up to two years imprisonment for submission of false records. |