Is a repaired motor less reliable?
Nailen, Richard
Posted 7-11-05
Is there is reason to suppose a properly repaired motor is
less reliable than a new machine?
RELIABILITY. CAPABLE OF BEING RELIED ON." That's the
entire definition, in at least two dictionaries, of the word.
Few definitions are less informative. Nevertheless, whereas
the effect of repairs on motor efficiency was an important
issue a few years ago, concern is now being expressed about
how repairs affect reliability.
In 1982, Heinz Bloch, a well-known authority on machinery
operation and maintenance, wrote a 680-page book titled Improving
Machinery Reliability (now in its 3rd edition). The author
mentions "reliability improvement," "increased
reliability," "optimum reliability," "high
reliability," "continued reliability," and
"maximum reliability." Yet nowhere does he define
the word reliability. As for electric motors, the book contains
only a brief 15-page section devoted only to basic motor technology
To most people, reliability is a measure of the degree to
which something works when called upon. If it doesn't work
half the time, we might consider it "only 50% reliable,"
or we might say "chances are only 50-50 it will work
at any given time." Assigning such numbers to reliability
involves statistical theory that's not so simple. We need
not go into the theory here. What we do need to examine more
closely is the meaning of "it works" versus "it
doesn't work."
Consider the automobile. One vehicle starts easily on cold
winter mornings and always reaches its destination-yet it
has a tendency to overheat, it leaks oil on the garage floor,
and there's always been that mysterious rattle. Is it more,
or less, reliable than the car displaying no audible or visible
defects, but that needs an annual brake overhaul, has a front
end that won't stay aligned, and gets terrible gas mileage?
Quantifying reliability
As for electric motors-one may be noisier than another, or
may exhibit out-of-tolerance vibration. How is "reliability"
to be quantified? Is motor reliability something like pornography-we
can't define it, but will know it when we see it?
Few technical definitions exist. Generally, though, the lower
the failure rate-the fewer failures of units over a given
time period-the higher the unit reliability.
But what is "failure"? The Edison Electric Institute
definition is: "Lack of one or more fundamental functions
which necessitates immediate removal from service." (See
Figure 1.) In a survey of 5,408 motors in electric utility
service, back in 1984, the annual failure rate over a six-year
period ranged from 0.9 to 2.6, depending upon the motor manufacturer.
(Worth noting: rotor and bearing troubles predominated; we'll
say more about that later.)
Reliability is sometimes stated as a percentage, according
to this formula:
in which N is the number of units in the population being
considered and R is the number of "failures" in
that set during the period studied. That concept is difficult
to apply to machines that may take a long time to repair a
single failure, when the period being examined is fairly short.
The lengthy downtime results in an actual reliability no greater
than that of another machine that fails more than once but
is repaired quickly.
A 1990 IEEE paper ("Reliability Improvement and Economic
Benefits of On-Line Monitoring Systems for Large Induction
Machines" by Siyambalapiliya and McLaren) presumes a
motor failure rate of 3% to 10%, defined as the number of
failures in a specific unit divided by a specific time span.
If a rate of 5% per year is taken as an example, the mathematics
of probability leads to the conclusion that there is a 4.75%
chance of one unit failing in any one year. Presumably that
would describe a unit reliability of 95.25%.
Just what is failure?
But again, "failure" needs some definition. Papers
on the subject often refer only to "catastrophic"
failure-which is not much help in defining what can happen
to a motor.
Many engineers have studied this issue over the past 30 years.
Numerous technical papers discuss their findings. Much of
that material, however, deals only with "large"
motors (above 500 horsepower, in present-day NEMA standard
terms). The most recent data appear in the IEEE Transactions
on Industry Applications, Volumes IA-21 (1985) and IA-23 (1987),
under the title "Report of Large Motor Reliability Survey
of Industrial and Commercial Installations." Previous
surveys, including other apparatus as well as motors, and
only in industrial plants, appeared in Volume IA-IO (1974);
still earlier results were published in 1962.
Such surveys have generally taken no account of age, condition,
or service history of individual units, nor was any allowance
made for variation in application or operating conditions
(such as annual hours of use, or relative severity of starting
duly).
Thousands of motors might ordinarily be considered an impressive
survey sample size. For polyphase a-c machines, however, the
variation in origin, rating, enclosure, and application is
so broad that such a cross-section hardly scratches the surface.
The research should not be dismissed as wholly irrelevant,
of course. Information of this kind is difficult to get because,
despite widespread emphasis on predictive maintenance, "trending"
of diagnostic data, and life-cycle cost analysis, few industrial
users keep sufficiently detailed records to support research
much beyond what the published surveys have accomplished.
Reliability information unreliable
Nevertheless, the concern about motor efficiency-leading
to utility rebate programs, to the EPACT legislation, to studies
of motor repair practices, and now to the development of NEMA's
"Premium Efficiency" products-have highlighted two
deficiencies in available reliability information.
The first has been lack of a definitive answer to this question:
'Are more-efficient motors inherently more reliable?"
Prior to the 1997 effective date of EPACT, promoters of higher-efficiency
designs (including the U.S. Department of Energy) often had
difficulty justifying the added investment in efficiency based
on energy cost savings alone. Some marketers implied (or claimed)
higher reliability and longer life for more efficient designs
as an added benefit.
Various reasons were given. The most common one was a presumed
reduction in motor operating temperature, said to lengthen
the life of both windings and bearings. However, such reasoning
was largely fallacious, because:
* Motors seldom fail because of winding overheating not involving
abuse such as blocked ventilation (Figure 2). Some authorities
estimate that 75% to 90% of all motor breakdowns involve the
rotor or originate with bearings.
* Furthermore, differences in ventilation systems (especially
smaller cooling fans to reduce windage loss) often cause a
motor with reduced losses to run at the same temperature as
the earlier, less efficient design. Temperature limits themselves
(either on the motor rating or on the insulation system) have
not changed for decades.
* Bearing operating temperature limits for all standard motors
are far below any danger point. The higher the actual bearing
temperature, the sooner relubrication will be needed-a condition
imposed by grease characteristics, not by the bearing itself.
Eventually, one manufacturer was able to publish comparative
data on "standard" (pre-EPACT) versus "energy
efficient" motor reliability (meaning failure rate).
Warranty claims were the basis. They showed no significant
difference between the two product lines. (See "Are energy
efficient motors reliable?" in EA October 1998.)
Any such comparison can be questioned on several grounds,
such as:
* What range of conditions was covered by the claims?
* Since warranty periods normally amount to only 12 to 36
months, while motor life spans are generally considered to
be 5 to 10 times that long, the comparison involves only infant
mortality (about which more later) and is not necessarily
representative of long-term performance.
* Obviously, only one manufacturer's products are included.
* The energy-efficient product was relatively new in the
marketplace. The ratio of warranty failures to units in service
could differ considerably for those motors compared to a much
broader, more widely used product line.
That particular comparison became largely irrelevant after
1997. Once the "energy efficient" EPACT design became
the new standard, the former standard was no longer a purchaser
option. Whether or not it was either more or less reliable
might be an ongoing cause of acrimony between user and manufacturer,
but not a valid reason to choose a different design.
However, when NEMA established the "Premium" line,
offering still higher efficiency, two alternatives (at differing
prices) once again became available. Some of the same arguments
surfaced again.
Although no definitive proof exists (or is likely to), the
claim of enhanced reliability based on "cooler running"
appears no more valid than before. That applies also to bearing
differences (which are largely non-existent). In any event,
the population of "Premium Efficiency" units now
in service is too small to provide trustworthy data.
The issue of sample size is an important one, because of
the nature of reliability, which continues to lack a consistent
definition for rotating machines. On the other hand, its significance
in electric power systems is well understood. The subject
merits a lengthy IEEE standard all to itself: IEEE 493, the
"Gold Book," titled Recommended Practice for Design
of Reliable Industrial and Commercial Power Systems.
Although the causes may be numerous, in many points of origin,
a system failure is easily defined. It consists in the interruption
of power flow sufficient to stop some operation not meant
to be stopped. "Power failure"-a "lights out"
condition-is not hard to define.
In contrast, "failure" of an electric motor may
have many meanings, including:
* Inability to start.
* Tripping off-line during running because of some winding
(or other) fault not immediately recognizable.
* Complete winding burnout.
* Damage within one or both bearings.
* A bent or broken shaft.
* A foreign object (such as a piece of hardware) appearing
inside the motor.
* A broken fan blade, resulting in dangerously high vibration.
Define failure by symptoms?
If we choose to define "failure" as the EEI has
("necessitating immediate removal from service"),
we have a problem. A motor that develops some internal noise,
or that becomes so dirty that it begins to overheat, represents
potential trouble-but is that "failure"? And look
again at "inability to start." When "energy
efficient" motors were developed, more than one plant
operator complained that "they won't start the load,"
whereas an older motor did. Both motors fully met NEMA standards,
but the accelerating torque for the "energy efficient"
design did not exceed standards by as much as the older design
did. The driven load itself was not standard; it demanded
more torque during starting, which was provided by the excess
margin of the old design. The understandable user conclusion
was that the higher-efficiency design was not "reliable."
But this cannot be termed "failure." It's a misapplication.
The foregoing list could go on much further. Clearly, because
many such "failures" are not the motor's fault,
they are not properly attributable to the motor design or
manufacture (again, see Figure 2). Any industry survey of
unit reliability is unlikely to unearth enough detail to sort
all that out. Plant records are probably going to show little
beyond the fact that the motor needed repair.
When first introduced, the "energy efficient" motor
commanded a higher price, and (as noted earlier) its reduced
energy cost was often too little incentive for the added investment.
That didn't matter once such designs were the only product
on the market.
Today's "Premium Efficiency" motor is optional,
however, as well as involving a premium price. Hence, taking
reliability comparisons a step further, the question now being
asked is this: Is a new, "Premium Efficiency" motor
inherently more reliable than a repaired motor of either the
pre-1997 or the EPACT type?
Intuitively, one might presume that any brand-new product
should prove more reliable than one having seen service (whether
repaired or not). The presumption is questionable, for many
reasons. The first one is infant mortality. Figure 3 shows
the "bathtub curve" (so-called because of its shape)
applicable to any product. Two of its characteristics deserve
attention. One is that early or "premature" failures
(in Region A) tend to considerably outnumber those occurring
after long service (Region B). Still later, of course, "wearout"
takes over, and the failure rate inevitably rises again. No
matter what quality level or design conservatism is achieved,
this curve shape will always apply.
A 1990 U.S. Navy examination of "reliability-centered
maintenance" concluded that: "These . . . studies
showed the assumption that the reliability of equipment always
decreased with age was incorrect. In fact, what was discovered
was the opposite. . . ."
The second point to keep in mind is that this is a statistical
probability variation. It can apply only to a large population
of identical units operating under identical conditions. It
says nothing about any individual unit, or several such units.
Consider ball bearings. Based on large-scale testing, and
statistical analysis, each bearing design is subject to an
"LJQ" life. When operated at rated load and speed,
with proper lubrication, 90% of all such bearings will last
as least as long as the "L^sub 10^" life in hours.
(Some may last much longer, although no one can say which
ones, or how much- sec Figure 4). But 10% of all such bearings
may fail any time before the LJQ period. One or more could
fail during the first revolution. Which 10% of any given group
of bearings will exhibit such behavior? No one can say.
A similar concept might apply to motors except for these
problems:
* A large enough group of identical units, under identical
conditions, is not to be found in the real world.
* The possible failure modes (however we choose to define
failure) are far more numerous than the simple metal fatigue
that usually ends bearing life.
Meaning of repair open to debate
Finally, of course, what do we mean by a repaired motor?
all these questions are pertinent:
* Repaired to what extent? That stay in (he repair shop may
have involved nothing more than a cleaning (Figure 5); the
bearings might have been replaced (whether or not they needed
it); rebalancing (Figure 6); a new shaft might have been installed
to replace a broken one; or the stator may have been rewound.
* Repaired in what manner! Did the shop adhere to industry
standards (ANSI AR-IOO), use materials in approved ways (such
as a UL-1446 insulation system), and employ accepted quality
management methods?
* Repaired how often? Is a motor that's had a failed bearing
replaced three times in IO years exhibiting more or less reliability
than one in the shop only once, but needing a complete rewind?
Even more important than what work was needed, or how often,
is the reason why work was needed. Far more motors are repaired
because of abuse or misapplication than because of some inherent
defect.
One may well interject at this point: "We're comparing
two motor designs here. Never mind what the real failure cause
was; one of them held up under that condition, the other one
didn't. So what's wrong with comparing?
The answer is: "Nothing, provided both motors-or, more
especially, both large groups of motors-really do experience
the same conditions." They need to be on identical drives,
subject to identical start/stop cycles, exposed to the same
temperature, ventilated by the same air, and lubricated the
same way.
That's unlikely enough for any two new motors. When one of
them has been "repaired," here's what can skew the
comparison:
* The lower the horsepower rating, the less likely machines
will be repaired at all following major damage (such as complete
winding burnout). But for lesser repairs, a motor may be taken
out of service several times throughout its useful lifetime.
How "reliable" it is following the first such repair,
or the fifth, cannot be estimated from any significant body
of data throughout industry. Failure rate statistics to support
reliability estimates for new "Premium Efficiency"
motors are equally non-existent and will necessarily remain
so for years to come.
* In many industrial settings, important motors are "spared."
When one goes out for servicing, a spare is put in its place.
Once the repaired motor comes back, it goes into "spare"
status, to remain out of service for months or years. Its
operating life cannot be compared to that of a companion motor
that didn't need servicing.
* If in storage for a long lime, the motor may be exposed
to hostile influences (such as high humidity, or building
vibration) not experienced by "identical" units
elsewhere. (See Figure 7.)
* The repaired motor may have been improved by the shop,
perhaps to mitigate a problem thought to have caused failure,
or perhaps because of the shop's desire to do a better job
based on experience. (See Figure 8.) Often, a conscientious
service center, once familiar with a customer's operating
problems, will add or enhance motor construction during the
repair process.
You'll hear something like this: "Oh, yes, that motor
needs [fill in your own experience], but they don't do that
at the factory. So we make sure it gets done during repairs
here." Extra winding taping or lacing, different impregnation,
Class H insulation in place of Class B or F, added bearing
seals-these render the motor no longer directly comparable
to another motor not altered in such ways.
Since the advent of higher-efficiency designs, numerous papers
and articles have drawn attention to the repair or replace
issue. However, any representative sampling of that literature
shows that the repaired versus new motor comparison was made
only on the differences in motor performance (particularly
the operating energy costs), the cost of repairs to a failed
unit, and the cost of a new motor. No concern was expressed,
by either manufacturers or the service industry, about relative
life expectancy of the new versus repaired unit.
It's true that those parts of a motor not replaced during
repair will remain just as old as they were when the motor
went into the shop. Except in the most severe applications,
or a truly catastrophic failure (which is likely to preclude
any conventional repair), that need not be a consideration
in the repair-or-replace decision. Some of the shaft's fatigue
life will have been used up. Rewinding a stator doesn't endow
a castaluminum rotor cage with new life. The laminations will
have aged. However, for standard integral horsepower motors,
those components rarely succumb to old age.
Based on all that, the following conclusions seem reasonable:
* Depending upon the nature of the repair process, a repaired
motor should not necessarily be any less "reliable"
than a new one, regardless of the latter's design. A complete
new stator winding, and new bearings, should be no more subject
to infant mortality than in a unit fresh from the factory.
* For those failures resulting from some inherent weakness
in the machine, a proper repair can eliminate the problem.
* Apples should be compared to apples. Comparing a new "Premium
Efficient" machine with a "repaired" EPACT
(or pre-EPACT) motor is not a valid match-up.
* If a motor of EPACT (or earlier) design has failed, the
cost to remove and either repair or replace it is a given.
Three options confront the user: repair it, whatever the design;
replace it with an EPACT-compliant unit; or replace it with
a "Premium Efficient" unit. The choice should be
made based on history, the nature of the application, the
prices (of removal and re-installation as well as repairs
or a new motor), and the energy costs-based on actual load
and actual usage, not the 8,700 hours-per-year hype of the
marketplace.
By Richard L. Nailen, P.E., EA Engineering Editor
|